I couldn't find any official documentation, but I did find that this topic was often mentioned in LEEDuser:
- Baseline for Ventilation Fan unconditioned space?
- Ventilation as Process Load
- the fan power of mechanical ventilation
- ventilation of unconditioned warehouse
- Mechanical Ventilation in some areas of building
According to them, the ventilation fan power in unconditioned zones should be treated as a process load and the ventilation fan power in the baseline case should be the same as the proposed case.
Any load not defined in ASHRAE 90.1 Appendix G appears to be treated as a process load.