Instead of directly manipulating mass flow rates, I would propose using Minimum Air Flow Fraction Schedule(s) for AirTerminal:SingleDuct:VAV:Reheat (or ...:noReheat), as shown below:

image description

(1) Setup Minimum Air Flow Fraction Schedules as Schedule:Constant

(2) Modify the schedule values according to your criteria by EMS instructions